Leckstar 5/G relay for JOLA leak detectors

Iskanje

Šifra: Leckstar 5/G


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • supply voltage: 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • power supply: approx. 3 VA
  • switching indicator: 1 red LED light when the electrode is wet / output relay is not energised
  • protection class: IP54
  • temperature range: -20 °C to +60 °C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

Description

The Leckstar 5/G relay for JOLA leak detectors is designed for limit level signalling. They shall be installed in a control cabinet or other suitable protective enclosure. The switches are suitable for use in clean environments.

  • no cable disconnection control function
  • for connecting all conductive electrodes
    without cable disconnection control unit
  • with 1 potential-free switching contact at the output

Electrode relay in surface-mount housing with transparent cover, with 1 LED for mains power indication and 1 LED for alarm status indication, inside the housing

Before use, we recommend viewing the attached pdf documents under the Documentation tab.

Leckstar 5/G features

  • supply voltage: 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • mains power indication: via 1 green LED
  • power supply: approx. 3 VA
  • electrode circuit. 2 terminals (under safety extra-low voltage SELV) operating on 1 output relay with switching self-test
  • no-load voltage: 18 Veff 10 Hz (safety low voltage SELV)
  • short-circuit current: max. 0.5 mAeff
  • response sensitivity: approx. 30 kW or approximately 33 µS (electrical conductivity)
  • Power circuit: 1 single-pole potential-free switching contact with quiescent current principle
  • switching indicator: 1 red LED light when the electrode is wet / output relay is not energised
  • switching voltage: max. AC 250 V
  • switching current: max. AC 4 A
  • switching power: max. 500 VA
  • housing: insulating material, with 3-cable input
  • connection: internal terminals
  • protection class: IP54
  • installation: surface mounting with 4 screws
  • orientation of installation: any
  • temperature range: -20 °C to +60 °C
  • max. Connecting cable length: 1,000 m between the electrode relay and the electrode(s)

For more information, please see the attached pdf documents under the Documentation tab.

Welcome to the article ”Conductive Measurement of Liquids”

Povpraševanje

    You may also like…