OWE/Ex-0G capacitive JOLA leakage detector in Ex version

Iskanje

Šifra: OWE/Ex-0G


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • EC type-examination certificate: INERIS 03ATEX0160
  • Housing: antistatic (conductive) PP and cast resin
  • connection cable: antistatic PURLF cable (with outer conductive PUR sheath), 2X0.75 mm2, length 5 m, longer on request up to 20 m
  • Protection class: IP65
  • temperature range: – 20°C to + 60°C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

,

Description

The OWE/Ex-0G capacitive leak detector JOLA in Ex version is suitable for use in areas where a fast and automatic alarm is required in the event of a leak. It is suitable for use when dealing with organic or inorganic liquids having a dielectric constant greater than 1.8.

The detectors can only be used in a temperature range between -20 °C and +60 °C, but despite the specified temperature range, use above freezing is recommended.

It is recommended for installation in rooms where excessive humidity is not expected under normal conditions.

It is recommended to install it at the lowest point in the room to ensure a quick alarm in case of leakage.

We recommend viewing the pdf documents under the Documentation tab before use

Operating mode OWE/Ex-0G

The capacitive measuring principle is mainly used to detect electrically non-conductive (insulating) liquids, but can also be used to detect electrically conductive liquids.

Electrically non-conductive liquids are usually organic liquids such as oils and solvents. The electrode assembly is a capacitor and the dielectric is air or liquid. The dielectric constant of air is 1. The dielectric constant of the liquid to be detected is higher. For our capacitive sensors, the dielectric constant must be greater than 1.8.

The capacitive leak detector recognises a change in the dielectric constant of the measuring capacitor and an alarm signal is triggered. The design of the measuring capacitor allows direct mounting on the ground and generally excludes the possibility of interference effects due to different substrates.

OWE/Ex-0G features

  • use: for use in intrinsically safe circuits in potentially explosive atmospheres Zone 0, 1 or 2
  • EC type-examination certificate: INERIS 03ATEX0160
  • Housing: antistatic (conductive) PP and cast resin
  • connection cable: antistatic PURLF cable (with outer conductive PUR sheath), 2X0.75 mm2, length 5 m, longer on request up to 20 m
  • Functional principle: capacitive sensor with gold-plated capacitor plates on epoxy resin substrate
  • self-capacitance: Ci = 220 nF + 200 pF per metre of connecting cable
  • self-inductance: Li = 1.1 mH + 1 µH per metre of connecting cable
  • Protection class: IP65
  • response height from the bottom edge of the housing: ≥ 12 mm (depending on the dielectric constant of the liquid)
  • temperature range: – 20°C to + 60°C
  • max. length of the connecting cable between sensor and relay: approx. 1.000 m

More technical information can be found in the datasheet under the Documentation tab.

Use

All organic and inorganic liquids with a specific dielectric constant of 1.8. It is a prerequisite that, depending on the ambient temperature, these fluids are present in liquid form and that the sensors to be used are sufficiently humidified. The response height is approximately 12 mm.

  • Fuel oil leak detection