Leckmaster 155 relay for JOLA leak detectors
Po naročilu. Pošljite povpraševanje.
Delivery time: okvirno 2 tedna
- supply voltage: 230 V AC other voltages on request
- Energy consumption: approx. 3 VA
- cable break monitoring: I < 0,15 mA
- breakdown voltage: max. AC 250 V
- switching current: max. AC 4 A
- switching power: max. 500 VA
Description
The Leckmaster 155 relay for JOLA leak detectors can be used to detect and signal leaks in electrically conductive and non-conductive liquids. The relay is suitable for installation in clean environments. The switching device is designed to be installed in a protective enclosure or cabinet.
- for connecting 5 CPE, OWE 2/C or COW capacitive sensors
- with cable disconnection control function
- with a touch button to acknowledge the alarm
- with two potential-free switching contacts at the output and
- with 5 20 V DC status signal outputs for building control system
Capacitive relay in upgrade housing, with transparent cover, with 5 x 3 LEDs to show operating status and 1 LED to show N-clear status, inside housing
Features of the Leckmaster 155
- supply voltage: 230 V AC other voltages on request
- Energy consumption: approx. 3 VA
- Sensor circuit: 5 terminals under safety extra-low voltage, for 5 signal lines without galvanic isolation from each other, with common earth connection.
- No-load voltage: DC 8.4 V (safety very low voltage)
- short-circuit current: < 10 mA
- response sensitivity: 1.5 mA 1.8 mA
- cable break monitoring: I < 0,15 mA
- first voltage circuit: 1 single-pole potential-free switching contact based on the operating current principle, for collective alarm in case of leakage or cable breakage, can be confirmed by touch key
- Second voltage circuit: 1 single-pole potential-free switching contact, based on the quiescent current principle, for group alarm in case of leakage or cable breakage
- breakdown voltage: max. AC 250 V
- switching current: max. AC 4 A
- switching power: max. 500 VA
- Status signal outputs for the building control system: 5 connections under safety extra-low voltage for a binary switched-state output signal of 20 V DC of each of the 5 signal lines, without galvanic isolation between them, with a common earth connection
- No-load voltage: 20 V DC (sufficient for 24 V inputs, as a high signal usually requires at least 15 V)
- short-circuit protection: short-circuit current limit ≤ 30 mA
Povpraševanje
You may also like…
For your victories, with our solutions. Call us:
Contact us.
Call us:
+386 (0)2 62 96 720
Email us:
[email protected]