KUR 5/K/BA JOLA compact ceiling mounted cooling controller
Po naročilu. Pošljite povpraševanje.
Delivery time: okvirno 2 tedna
- supply voltage: standard 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
- input power: approx. 3 VA
- switching voltage: max. 250 V AC
- switching current: max. 4 A AC
- switching power: max. 500 VA
- temperature range: – 20 °C to + 60 °C
Description
The KUR 5/K/BA compact cooling ceiling regulator JOLA is used to detect, measure moisture on copper pipe.
Conductive relay for mounting on copper pipe.
The KUR 5/K/.. compact ceiling controllers are designed to measure the moisture between the printed leads of the FTS/KO-1 film sensor mounted on a plate at the bottom of the enclosure, and to switch the built-in relay output when the set sensitivity level is reached, allowing the activation of an external solenoid valve.
Compact ceiling controllers for cooling have a protection circuit design: the potential-free switching contact is in quiescent current – in other words, the relay is energised when the sensor is dry.
Before use, we suggest you view the attached pdf documents under the Documentation tab.
KUR 5/K/BA features
- Scope of application: for attachment to copper pipe with an outer diameter between 25 mm and 32 mm
- Voltage: 24 V AC (SELV low-voltage safety)
- Energy consumption: approx. 3 VA
- control circuit: 2 terminals (under safety extra-low voltage SELV) operating on 1 output relay without self-testing
- No-load voltage: 9 Veff 10 Hz (safety extra-low voltage SELV)
- short-circuit current: 0.3 mA
- response sensitivity: approx. 50 kOhm or approximately 20 µS (electrical conductivity)
- control circuit: 1 single-pole potential-free switching contact without self-restraint
- Functionality: based on the principle of quiescent flow
- switching voltage: max. 24 V AC (safety extra-low voltage SELV)
- switching current: max. 4 A AC
- housing: insulating material, with 2 M 20 x 1.5 cable entries
- connection: internal terminals
- IP degree of protection: IP 54
- mounting: on copper pipe using a belt clip
- mounting orientation: any
- Temperature range: > 0 °C to + 60 °C
More technical information can be found in the attached pdf under the Documentation tab.