KUR 5 JOLA cooling ceiling controller

Iskanje

Šifra: KUR5


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • supply voltage: standard 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • input power: approx. 3 VA
  • switching voltage: max. 250 V AC
  • switching current: max. 4 A AC
  • switching power: max. 500 VA
  • temperature range: – 20 °C to + 60 °C
za merjenje nivoja tekočin, detekcija uhajanja

Description

The KUR 5 JOLA cooling ceiling controller is designed for installation in a control cabinet, with connection terminals on the front of the housing and an LED warning or alarm light. The KUR 5 relay unit is designed to measure the humidity between the FTS/KO-1 film moisture detector and the switch.

Conductive relay for U- or surface mounting, with connection terminals on top of the housing and red LED for moisture indication.

The unit is designed to be mounted or installed in a switch box in a suitable protective enclosure and can therefore only be mounted/installed in these locations. It is only suitable for use in clean environments.

The KUR 5 control ceiling is designed to measure the moisture between the printed conductors of the FTS/KO-1 film sensor and to switch the built-in output relay when the set sensitivity level is reached, allowing the activation of an external solenoid valve.

The cooling ceiling controller is in a protection circuit design: the potential-free switching contact is in quiescent current – in other words, the relay is energised when the sensor is dry.

Features of KUR 5

  • supply voltage: standard 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • input power: approx. 3 VA
  • control circuit: 2 terminals (under safety extra-low voltage SELV) operating on 1 output relay without self-control
  • no-load voltage: 18 Veff 10 Hz (safety extra-low voltage SELV)
  • short-circuit current: 0.3 mA
  • response sensitivity: approx. 50 kOhm or approximately 20 µS (electrical conductivity)
  • control circuit: 1 single-pole potential-free switching contact without self-restraint
  • Functionality: based on the principle of quiescent flow
  • LED indicators: 1 red LED when sensor is wet/relay is not energised
  • switching voltage: max. 250 V AC
  • switching current: max. 4 A AC
  • switching power: max. 500 VA
  • housing: insulating material, 75 x 55 x 110 mm
  • connection: terminals on the housing
  • IP degree of protection: IP 20
  • mounting: U-bar fixing to DIN 46277 and EN 50022 or fixing via 2 drill holes
  • mounting orientation: any
  • temperature range: – 20 °C to + 60 °C
  • maximum length of the connection cable between relay and sensor: 500 m

Povpraševanje