KUR 5/G JOLA cooling ceiling controller

Iskanje

Šifra: KUR5/G


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • supply voltage: standard 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • input power: approx. 3 VA
  • switching voltage: max. 250 V AC
  • switching current: max. 4 A AC
  • switching power: max. 500 VA
  • temperature range: – 20 °C to + 60 °C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

Description

The KUR 5/G cooling ceiling controller JOLA is a relay with an external mounting housing, which is made of a transparent cover. It contains a green LED indicator light and a red LED light to indicate the humidity inside the housing. For connection to the FTS/KO-1 film sensor.

Conductive relay in an upgrade housing with transparent cover, green LED for mains monitoring and red LED for moisture indication in the housing.

The KUR 5/G control ceiling is designed to measure the moisture between the printed conductors of the FTS/KO-1 film sensor and to switch the built-in output relay when the set sensitivity level is reached, allowing the external solenoid valve to be activated.

The cooling ceiling controller is in a protection circuit design: the potential-free switching contact is in quiescent current – in other words, the relay is energised when the sensor is dry.

KUR 5/G features

  • supply voltage: standard 230 V AC; on request: 240, 115, 24 V AC or 24, 12 V DC
  • Network monitoring indicator: 1 green LED
  • input power: approx. 3 VA
  • electrode circuit: 2 terminals (under safety extra-low voltage SELV) operating on 1 output relay without self-restraint
  • no-load voltage: 18 Veff 10 Hz (safety extra-low voltage SELV)
  • short-circuit current: 0.3 mA
  • response sensitivity: approx. 50 kOhm or approximately 20 µS (electrical conductivity)
  • control circuit: 1 single-pole potential-free switching contact without self-restraint
  • Functionality: based on the principle of quiescent flow
  • LED indicators: 1 red LED (contact open)
  • switching voltage: max. 250 V AC
  • switching current: max. 4 A AC
  • switching power: max. 500 VA
  • housing: insulating material, with 3 screw connections
  • connection: internal terminals
  • IP degree of protection: IP 54
  • mounting: using 4 screws
  • mounting orientation: any
  • temperature range: – 20 °C to + 60 °C
  • maximum length of the connection cable between relay and sensor: 500 m