  • supply voltage: 230 V AC; on request: 240, 115, 24 V AC, 24, 12 V DC
  • control circuit: 2x NC contacts based on quiescent current principle, both activated in standby mode. (more in the datasheet)
  • Functionality: quiescent flow principle
  • protection class: IP20
  • temperature range: -20 °C to +60 °C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

Description

The ESA 2 alarm relay JOLA is designed for limit level signalling (sensor 1) or for two-point monitoring (sensor 2). They shall be installed in a control cabinet or other suitable protective enclosure. The switches are suitable for use in clean environments.

Electronic alarm relay for mounting or mounting on DIN rail via 2 drill holes, with connection terminals on top of the housing and with 1 built-in two-colour LED to indicate the corresponding switching status.

This unit is designed to be mounted or installed in a switch box in a suitable protective enclosure and can therefore only be installed in these locations. It is only suitable for use in clean environments.

The design of the electrode alarm relay is based on the quiescent current principle, in other words, an alarm signal is given if there is no connection between terminals 7 and 8; the 2 NC output contacts of the unit also return to the alarm state if the supply voltage fails.

In standby mode (the unit is supplied with voltage and a connection between terminals 7 and 8), both potential-free output contacts are in the activated state (= open) and the two-colour LED is green.

In case of alarm (unit energised and no connection between terminals 7 and 8), the potential-free NC output contacts are in an inactive state (= closed) and the two-colour LED flashes red.

Output relay 1 can be reset with the built-in acknowledge button or the connected external acknowledge button (connection option on terminals 4 and 5) to cancel an alarm transmitted via this output. The LED then stops flashing and returns to solid red.

ESA 2 features

  • supply voltage: 230 V AC; on request: 240, 115, 24 V AC, 24, 12 V DC
  • input power: approx. 3 VA
  • electrode circuit: 2 terminals (under safety extra-low voltage SELV) operating on 2 output relays without self-checking (1 output relay can be reset if an alarm is activated)
  • No-load voltage: 9 Veff 10 Hz (safety extra-low voltage SELV)
  • short-circuit current: max. 0.5 mAeff
  • response sensitivity: approx. 30 kW or approximately 33 µS (electrical conductivity)
  • Control circuit: 2 potential-free normally closed contacts according to the quiescent current principle, both activated in standby mode. (more in the datasheet)
  • Functionality: quiescent flow principle
  • status indicators: two-colour LED green, red (see datasheet for details)
  • switching voltage: max. 250 V AC
  • switching current: max. 4 A AC
  • switching power: max. 500 VA
  • housing: insulating material, 75 x 55 x 110 mm
  • connection: terminals on the housing
  • protection class: IP20
  • mounting: on 35 mm DIN rail or fixing via two drill holes
  • orientation of installation: any
  • temperature range: -20 °C to +60 °C
  • length of connecting cable: max. 1,000 m between safety relay and sensor