  • Accuracy: 0.15 % FS
  • input signal: 0(4) … 20 mA
  • output signal: 0(4) … 20 mA
  • test voltage: 2.5 kV, 50 Hz
  • Operating voltage: 600 V AC/DC
  • operating temperature: 0 °C … +55 °C
INOR

Description

The IsoPAQ-110L single and dual channel isolator with loop for 0(4)-20 mA INOR current signals, is used for electrical isolation to avoid measurement errors due to different voltage potentials or ground loops in the instrument installation.

The dual-channel version of the IsoPAQ-110L offers an affordable alternative combined with a space-saving fixing. The isolator does not require an external power supply, which contributes to lower installation costs. High reliability ensures safe system operation and low maintenance costs.

 

Features of the IsoPAQ-110L

  • input and output are galvanically isolated:
    protection against false measurements due to parasitic voltages or earth loops
  • 1- and 2-channel version:
    allows optimum cost-effectiveness
  • no power supply required:
    shortened wiring saves installation costs
  • Fixed zones:
    ready to use without any settings
  • safe isolation according to EN 61140:
    design and high level of isolation (2.5 kV) provide protection for service personnel and downstream equipment against unacceptably high voltages
  • compact DIN-rail mounting:
    11.2 mm housing combined with very low self-heating for space-saving (˝high-density˝) mounting
  • Type: passive, 1- and 2-channel

 

ELPRO Lepenik offers technical support (TP-1, 30 min) and calibration.