T6445 CO2 concentration, relative humidity and temperature meter with RS485 interface, COMET channel carrier

Iskanje

Šifra: T6445


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

Temperature

  • measuring range: -30 … +60 °C
  • Accuracy: ±0.4 °C

Relative humidity

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH

CO2

  • measuring range: 0 … 2000 ppm
  • Accuracy: ±50 ppm + 2 % of reading at 25 °C and 1013 hPa

General information

  • ambient temperature: -30 … +60 °C
  • Output: RS485
  • Power: 9-30 V DC
  • Protection classes: IP 30 electronics, IP 40 sensors
  • dimensions: 89 x 73 x 240 mm
COMET

Description

T6445 CO2 concentration, relative humidity and temperature meter with RS485 interface for Web Sensor channel installation.

The multi-point CO2 and temperature adjustment process leads to excellent CO2 measurement accuracy over the entire operating temperature range, which is essential for process control and external applications.

The dual-wavelength NDIR CO2 detection process automatically compensates for the effects of ageing. The CO2 module is highly resistant to contamination and offers maintenance-free operation and extremely long term stability.

 

A visual display of the CO2 concentration in the air:

  • green: CO2 concentration 0 … 1000 ppm
  • bright yellow: CO2 concentration 1001 … 1200 ppm
  • illuminated red: CO2 concentration 1201 ppm or more

 

Benefits

  • resistant to pollution and environmental influences
  • long-term stability
  • optimum maintenance-free operation
  • exceptional precision

 

Features of the T6445

Temperature sensor

  • measuring range: -30 … +60 °C
  • Accuracy: ±0.4 °C
  • resolution: 0.1 °C

Humidity sensor

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH
  • resolution: 0.1 % RH

Rosišče (dew point)

  • measuring range: -60 … +80 °Cdp
  • Accuracy: ± 1.6 °Cdp at room temperature T<25 °C and humidity>30%
  • resolution: 0.1 °Cdp

CO2 sensor

  • measuring range: 0 … 2000 ppm
  • Accuracy: ±50 ppm + 2 % of reading at 25 °C and 1013 hPa
  • resolution: 1 ppm

 

GENERAL TECHNICAL DATA

  • ambient temperature: -30 … +60 °C
  • Output: RS485
  • communication protocols: ModBusRTU, ARION, Advantech ADAM
  • Power: 9-30 V DC
  • Protection classes: IP 30 electronics, IP 40 sensors
  • dimensions: 89 x 73 x 240 mm
  • Stem length: 130 mm
  • weight: 150 g
  • Warranty: 3 years
  • Set contains: T6445, user manual, calibration certificate with traceability, FREE TSensor software for transducer configuration

 

You can find much more useful information in the Documentation tab.