The JOLA S 2M/PP bar electrode is designed to signal the presence of an electrically conductive liquid caused, for example, by a burst pipe, via a connected relay.
Conductive bar electrodes must only be used in normally dry environments.
They can be installed from the top or the side. In both cases, ensure that the tips of the poles are only slightly above the ground to be controlled.
The conductive electrodes are equipped with two sensitive elements in the form of two electrode rods: 1 control electrode and 1 earth electrode. If two non-insulated surfaces of the electrode rod sensor come into contact with an electrically conductive liquid (e.g. water, acid, etc.), electrical contact is established and an alarm signal is emitted.
Before use, we recommend viewing the attached pdf documents under the Documentation tab.
S 2M/PP properties
Design: 1 control electrode and 1 earth electrode
Sensitive element: 2 electrode plates of 316 Ti stainless steel, each 4 mm diameter, covered with a polyolefin shrink tube, standard length: 300 mm each
max. length of the bar: approx. 2,500 mm
Threaded socket: PP, G1
electrical connection: connection head made of PP (on request: cast aluminium)
Protection rating: IP54
temperature range: -20 °C to +60 °C (higher temperatures on request)
cable break control: none
Classification:
Leckstar 5 or Leckstar 5/G: any number of the above electrodes can be connected in parallel to one of these relays.
length of connecting cable: 1,000 m between the electrode relay and the rear electrode
For more information, please see the attached pdf documents under the Documentation tab.
Examples of use
Use of a bar electrode to detect leakage of an electrically conductive liquid in the outer pipe of a two-pipe system
Use of a bar electrode to detect leakage of an electrically conductive liquid at the lowest point (groove in the figure) of the collecting room