S 2 M/PVDF-LS4 JOLA bar electrode

Iskanje

Šifra: S 2 M/PVDF-LS4


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • Design: leakage detector with relay output
  • electrode rods: 2 316 Ti stainless steel rods; other materials (e.g. titanium, Hastelloy, Monel or tantalum) on request;
  • Spigot: G1, PVDF
  • protection class: IP 54
  • temperature range: – 20 °C to + 60 °C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

Description

The S 2 M/PVDF-LS4 JOLA bar electrode signals via an electrode relay the presence of a liquid medium due to, for example, a burst pipe. Floor electrodes are designed for use in dry rooms.

S 2 M/PVDF-LS4 with integrated galvanic separation:

  • prevents interconnection of electrode circuits
  • prevents the formation of earth loops when more than one detector is connected to a common power supply circuit.

Conductive rod electrodes must only be used in normally dry environments. They can be installed from the top or the side. In both cases, ensure that the tips of the electrode rods are only slightly above the ground to be controlled.

The conductive rod electrodes S 2 M / PP -…, S 2 M / PVDF -… and S 2 AM -… are equipped with two separate electrodes in the form of two electrode rods: 1 control electrode and 1 ground electrode. As soon as the conductive liquid creates a conductive path between the two electrode rods, the switching state of the leak detector changes.

Conductive measurement principle

The principle of conductive measurement is used to detect electrically conductive liquids. Not suitable for the detection of electrically non-conductive liquids.

Electrically conductive liquids are usually aqueous solutions of salts, acids or alkalis. In water, the molecules of these substances separate into positive and negative ions, which give the aqueous solution its electrical conductivity. The conductive leak detector detects the presence of an electrically conductive liquid and then sounds an alarm.

The measurement process uses alternating current to ensure accurate response sensitivity and to prevent galvanic processes at the electrodes. The conductive leak detector shall have an integrated electronic evaluation unit with galvanically isolated circuits. This prevents the electrode circuits from interconnecting and forming earth loops if more than one of these leakage detectors is connected.

Reliable detection of liquids with poor electrical conductivity, such as condensate or demineralised water, is ensured by the factory-set sensitivity response of the conductive leak detector.

Features S 2 M/PVDF-LS4

  • Design: leakage detector with relay output
  • electrode rods: 2 316 Ti stainless steel rods; other materials (e.g. titanium, Hastelloy, Monel or tantalum) on request
  • Length: on request (measured from the sealing surface of the spigot)
  • max. Length: 2.500 mm
  • Spigot: G1, PVDF
  • Electrical connection: four-wire connection via four-pole terminal block for max. 2.5 mm² in PP connector head with cable entry M 20 x 1.5
  • protection class: IP54
  • supply voltage: only for connection to extra low voltage SELV or PELV! (see datasheet)
  • Energy consumption: approx. 0.5 VA
  • Output: potential-free quiescent current contact (NC), max. load AC/DC 5 … 24 V (very low voltage SELV or PELV only); AC/DC 1 mA … 3 (1) A; wire colours: black and dark grey
  • switching condition without supply voltage: output relay de-energised, output contact open
  • switching capacitor for condition detection not activated: output relay energised, output contact closed
  • switching capacitor for state detection is activated: output relay de-energised, output contact open
  • cable break control: control of cable breakage due to quiescent current
  • galvanic isolation: only for connection to extremely low voltage SELV or PELV! voltage resistance > 500 V between capacitor circuit, supply circuit and output circuit
  • max. no-load voltage across the sensing capacitors: 5 Veff 15 kHz
  • max. short-circuit current on sensing capacitors: 0.2 mA
  • response sensitivity: approx. 30 kΩ or approx. 33 μS (conductivity)
  • temperature range: – 20 °C to + 60 °C

For more technical information, please refer to the datasheet attached under the Documentation tab.

Example of use of S 2 M/PVDF-LS4: monitoring false floors in the server room using a cable electrode and a panel electrode in the adjacent room.

Welcome to the article ”Conductive Measurement of Liquids”