OWE-SPS3 JOLA hanging electrode

Iskanje

Šifra: OWE-SPS3


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

  • design: leakage detector with current switching / NC (interrupting)
  • Housing: PP and cast resin
  • Electrical connection: three-wire connection via 3 x 0,75 connecting cable, 5 m long,
  • temperature range: – 20 °C to + 60 °C
za merjenje nivoja tekočin, detekcija uhajanja


Področja:

Description

The OWE-SPS3 JOLA hanging electrode signals via an electrode relay the presence of a liquid medium due to, for example, a burst pipe. Floor electrodes are designed for use in dry rooms.

OWE-SPS3 with integrated galvanic separation:

  • prevents the electrode circuits from interfering with each other
  • prevents the formation of earth loops when more than one detector is connected to a common power supply circuit.

Capacitive suspension sensors OWE -… must only be used in normally dry environments.

They must be installed with the sensor facing downwards. Three gold-plated PCBs are integrated in a capacitive suspension sensor of type OWE -….. The two outer single-sided gold-plated PCBs as screening electrodes and the double-sided gold-plated inner PCB as measuring electrode form a double capacitor. As soon as a non-conductive liquid flows into the space between the PCBs, the capacitance between the PCBs changes, as well as the switching state of the leak detector. If a conductive liquid is present, the boards are conductively bridged, which also causes a change in the switching state of the leak detector.

Capacitive measurement principle

The capacitive measuring principle is mainly used to detect electrically non-conductive (insulating) liquids, but can also be used to detect electrically conductive liquids.

Electrically non-conductive liquids are usually organic liquids, similar to oils and solvents. The electrode assembly is a capacitor and the dielectric is air or liquid. The dielectric constant of air is 1. The dielectric constant of the liquid to be detected is higher. For our capacitive sensors, the dielectric constant must be greater than 2 (CPE type) or 1.8 (OWE and COW type).

The capacitive leak detector recognises a change in the dielectric constant of the measuring capacitor and an alarm signal is triggered. The design of the measuring capacitor allows direct mounting on the ground and generally excludes the possibility of interference effects due to different substrates. The capacitive leak detector shall have an integrated electronic evaluation unit with galvanically isolated circuits. This prevents sensor circuits from interconnecting and forming earth loops if more than one of these leak detectors is connected and where the fluid detected is conductive.

Features of the OWE-SPS3

  • design: leakage detector with current switching / NC (interrupting)
  • sensing capacitors: 2 external single-sided gold-plated PCBs and 1 internal double-sided gold-plated PCB form a double capacitor
  • Housing: PP and cast resin
  • electrical connection: three-wire connection via 3 x 0,75 connecting cable, 5 m long; fitted with halogen connecting cable on request
  • supply voltage: only for connection to extra low voltage SELV or PELV! (see datasheet)
  • Energy consumption: max. 0.5 W
  • output: PNP transistor output wired via a 2 kΩ … 7,5 kΩ downstream input resistor; wire colour: black
  • short-circuit protection: at transistor output, Ik < 30 mA
  • switching condition without supply voltage: low signal
  • switching capacitor for state detection is not activated: the output of the PNP transistor carries the directional supply voltage = high signal
  • switching capacitor for state detection is activated: the output of the PNP transistor carries the directional supply voltage = low signal
  • cable break control: control of cable breakage due to quiescent current
  • galvanic isolation: only for connection to extremely low voltage SELV or PELV! voltage resistance> 500 V between capacitor circuit, supply circuit and transistor output
  • max. no-load voltage across the sensing capacitors: 5 Veff 40 kHz (safety extra-low voltage SELV)
  • max. short-circuit current on sensing capacitors: 0.2 mA
  • min. dielectric constant of the liquid to be detected: 1.8
  • temperature range: – 20 °C to + 60 °C

For more technical information, please refer to the datasheet attached under the Documentation tab.

Application example OWE-SPS3: fuel oil leak detection

Povpraševanje