IsoPAQ-641 high performance isolation converter for INOR current and voltage signals
Sale!
V zalogi.
- the input signal:
0 … 20 mA, 0 … 10 V, 0 … 5 V
4 … 20 mA, 2 … 10 V, 1 … 5 V - output signal:
0 … 20 mA, 0 … 10 V, 0 … 5 V
4 … 20 mA, 2 … 10 V, 1 … 5 V - Power supply: 24 V DC voltage range 16.8 V… 31.2 V, approx. 0.7 W
- operating temperature: -25 °C … +70 °C
- Accuracy: 0.1 % FS
- Operating voltage: 600 V AC/DC
Description
The IsoPAQ-641 high performance isolation converter for INOR current and voltage signals with calibrated range selection is used for isolation and conversion of standard signals.
The input and output range as well as the cutoff frequency of the IsoPAQ-641 can be easily configured using a DIP switch. No additional adjustment is needed due to the calibrated range.
Auxiliary power can be supplied via the terminals or via the optional In-Rail-Bus connector. There is a green LED light on the front of the unit for power monitoring.
Main features of IsoPAQ-641
- calibrated signal adjustment via DIP switch:
adjustable input and output range via DIP switch – high precision without further adjustments
- 3-input isolation:
protection against false measurements due to parasitic voltages or earth loops
- extremely slim design:
6.2 mm slim housing for easy and economical DIN rail mounting
- Optional In-Rail-Bus attachment connector:
allows fast and economical installation
- Safe isolation according to EN 61140:
protects service personnel and downstream equipment from unacceptable high voltage
- Maximum reliability:
no maintenance costs
Technical features
- input
resistance: current input ≤ 25 Ω, voltage input ≥ 100 kΩ
overload: current input < 50 mA, voltage input < 30 V
- output
load: output current ≤ 12 V (600 Ω at 20 mA), output voltage ≤ 5 mA (2 kΩ at 10 V)
linear transmission range: -1 … +110 %
residual ripple: < 10 mVrms
- general information
-3d cutoff frequency: 5 kHz, 100 Hz, 10 Hz
T99 response time: 150 µs, 7 ms, 70 ms
Test voltage: 3 kV AC, 50 Hz, 1 min
protection against electric shock: safe isolation according to EN 61140 with reinforced insulation according to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination level 2 between all circuits
ELPRO Lepenik offers technical support (TP-1, 30 min) and calibration.
Povpraševanje
You may also like…
For your victories, with our solutions. Call us:
Contact us.
Call us:
+386 (0)2 62 96 720
Email us:
[email protected]