IsoPAQ-632 2-channel INOR current and voltage signal splitter and repeater
Po naročilu. Pošljite povpraševanje.
Delivery time: approximately 2-3 weeks
- the input signal:
0 … 20 mA, 0 … 10 V, 0 … 5 V
4 … 20 mA, 2 … 10 V, 1 … 5 V - output signal:
0 … 20 mA, 0 … 10 V, 0 … 5 V
4 … 20 mA, 2 … 10 V, 1 … 5 V - operating temperature: -25 °C … +70 °C
- Accuracy: 0.1 % FS
- Operating voltage: 600 V AC/DC
Description
The IsoPAQ-632 two-channel INOR current and voltage signal splitter and repeater is used for isolation, conversion and distribution of 0/4 … 20 mA, 0/1 … 5 V and 0/2 … 10 V standard signals. The measurement input can also feed a loop for 2-wire inverters.
The input and two isolated outputs can be easily configured using a DIP switch. No additional adjustment is needed due to the calibrated range. The auxiliary power supply of the IsoPAQ-632 can be supplied via the terminals or via the optional In-Rail-Bus connector. There is a green LED light on the front of the unit for power monitoring.
Main features of the IsoPAQ-632
- calibrated signal adjustment via DIP switch:
input and output adjustable via DIP switch – high precision without further adjustments - 4-input insulation:
protection against erroneous measurements due to parasitic voltages or earth loops - Extremely slim design:
6.2 mm slim housing for easy and economical DIN rail mounting - optional In-Rail-Bus attachment connector:
enables fast and economical installation - safe separation according to EN 61140:
protects service personnel and downstream equipment from unacceptably high voltage - maximum reliability:
no maintenance costs
Technical features
- input
resistance: current input ≤ 35 Ω, voltage input ≥ 100 kΩ
overload: current input < 50 mA, voltage input < 30 V
Tx converter power supply: 16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA) - output
load: output current ≤ 6 V (300 Ω at 20 mA), output voltage ≤ 5 mA (2 kΩ at 10 V)
Linear transmission range: -1 … +110 %
residual ripple: < 10 mVrms - general information
number of channels: 2
-3d cutoff frequency: -3 dB 5 kHz
T99 response time: 150 µs
Test voltage: 3 kV AC, 50 Hz, 1 min
protection against electric shock: safe isolation according to EN 61140 with reinforced insulation according to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination level 2 between all circuits
EMC standard: EN 61326-1
ELPRO Lepenik offers technical support (TP-1, 30 min) and calibration.