T0210 COMET relative humidity and temperature transmitter

Iskanje

Šifra: T0210


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

Temperature sensor

  • measuring range: -30 … +80 °C
  • Accuracy: ±0.4 °C

Humidity sensor

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH from 5 to 95 % at 23 °C

Rosišče (dew point)

  • measuring range: -60 … +80 °C
  • Accuracy: ±1.5 °C at room temperature T < 25 °C and RH > 30%

GENERAL TECHNICAL DATA

  • ambient temperature: -30 … +80 °C
  • input: 0-10 V, outputs are not galvanically isolated
  • Power: 15-30 V DC; maximum consumption 20 mA; 24 V AC
  • Protection class: IP 65 electronics; IP 40 sensors
COMET

Description

The T0210 relative humidity and temperature transmitter contains a microprocessor-based control circuit in a rugged plastic housing with connection terminals.

The measured moisture value can be converted into the following format: dew-point temperature, absolute humidity, specific humidity, mixing ratio or other.

The transducer is equipped with two galvanically isolated current outputs. Computer processing allows temperature compensation of the humidity sensor and error display.

The built-in capacitive polymer humidity sensor ensures long-term stability of the humidity calibration, independent of the influence of water and condensation. The converter is useful for measurements in a non-aggressive environment.

 

Features of T0210

Temperature sensor

  • measuring range: -30 … +80 °C
  • Accuracy: ±0.4 °C
  • resolution: 0.1 °C

Humidity sensor

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH from 5 to 95 % at 23 °C
  • resolution: 0.1 % RH

Rosišče (dew point)

  • measuring range: -60 … +80 °Cdp
  • Accuracy: ±1.5 °Cdp at room temperature T < 25 °C and RH > 30%
  • resolution: 0.1 °Cdp

GENERAL TECHNICAL DATA

  • ambient temperature: -30 … +80 °C
  • input: 0-10 V, outputs are not galvanically isolated
  • Power: 15-30 V DC; maximum consumption 20 mA; 24 V AC
  • Protection class: IP 65 electronics; IP 40 sensors
  • dimensions: 88,5 x 170 x 39,5 mm
  • Stem length: 75 mm
  • weight: 150 g
  • Warranty: 3 years
  • Set includes: the T0210, user manual, calibration certificate with traceability, FREE TSensor software to configure the transmitter

 

Areas of use, applications

  • Building automation and HVAC management,
  • warehouses,
  • greenhouses,
  • production facilities,
  • museums/archives/galleries,
  • air-conditioned rooms,
  • weather stations.

 

You can find much more useful information in the Documentation tab.