H7430 relative humidity, temperature and atmospheric pressure transmitter with RS485 COMET output

Iskanje

Šifra: H7430


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

Temperature

  • operating temperature range: -30 … +80 °C
  • Accuracy: ±0.4 °C

Invests

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH at 5 % … 95 % and 23 °C

Pressure

  • measuring range: 600 … 1100 ppm
  • Accuracy: ±1.3 hPa at 23 °C from 800 to 1100 hPa

General information

  • ambient temperature: -30 … +80 °C
  • Output: RS485
  • Power: 9-30 V DC
  • Protection class: IP 54 electronics, IP 40 sensors
  • dimensions: 136 x 213 x 45 mm
COMET

Description

H7430 relative humidity, temperature and atmospheric pressure transmitter with RS485 output and two relay outputs for outdoor and indoor use.

The inverter is equipped with two relay outputs for displaying alarms or controlling external devices. It has three binary inputs to detect water, smoke, glass breaks or door contact.

The measured values can also be converted into other formats such as dew-point temperature, absolute humidity, specific humidity, mixing ratio or others. The device has a built-in capacitive polymer humidity sensor that ensures long-term stability of the humidity calibration, independent of the influence of water and condensation. The converter is useful for measurements in non-aggressive environments.

The H7430 contains a microprocessor-based control circuit housed in a rugged plastic enclosure with connection terminals. The sensor contains a stainless mesh filter. Computer processing allows long-term stability and error display.

 

Features H7430

Temperature sensor

  • measuring range: -30 … +80 °C
  • Accuracy: ±0.4 °C
  • resolution: 0.1 °C

Humidity sensor

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH at 5 … 95 % and 23 °C
  • resolution: 0.1 % RH

Rosišče (dew point)

  • measuring range: -60 … +80 °Cdp
  • Accuracy: ±1.5 °Cdp at room temperature T<25 °C and RH>30%
  • resolution: 0.1 °Cdp

Atmospheric pressure sensor

  • measuring range: 600 … 1100 ppm
  • Accuracy: ±1.3 hPa at 23 °C from 800 to 1100 hPa
  • resolution: 0.1 hPa

RELATED EXITS

  • quantity: 2
  • maximum voltage: 50 V
  • maximum current: 2 A
  • Maximum power: 60 VA

BINARY ENTRANCES

  • quantity: 3
  • minimum pulse duration on binary input: 500 ms
  • open contact voltage: <3.3 V
  • Low voltage: 0 … +0.5 V
  • high voltage level: +3.0 … +30 V

 

GENERAL TECHNICAL DATA

  • ambient temperature: -30 … +80 °C
  • Inputs: internal humidity, temperature and atmospheric pressure sensor
  • Output: RS485
  • Power: 9-30 V DC
  • Protection class: IP 54 electronics, IP 40 sensors
  • Communication protocols ModBus RTU, ARION and Advantech ADAM
  • dimensions: 136 x 213 x 45 mm
  • Stem length: 75 mm
  • weight: 360 g
  • Warranty: 3 years
  • Set includes: the H7430, user manual, calibration certificate with traceability and FREE TSensor software to configure the transducer

 

Areas of use, applications

  • controlling and monitoring temperature,
  • server rooms,
  • telecommunications equipment,
  • warehouses and greenhouses,
  • production premises,
  • museums, archives, galleries,
  • air-conditioned rooms,
  • HVAC applications.

 

You can find much more useful information in the Documentation tab.

Povpraševanje