H6020 temperature, humidity and CO2 controller with two COMET relay outputs

Iskanje

Šifra: H6020


Po naročilu. Pošljite povpraševanje.

Delivery time: okvirno 2 tedna

Temperature

  • operating temperature range: -30 … +80 °C
  • Accuracy: ±0.4 °C

Invests

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH at 5 % … 95 % and 23 °C

For CO2

  • measuring range: 0 … 2000 ppm
  • Accuracy: ±50 ppm + 2 % of reading at 25 °C and 1013 hPa

General information

  • ambient temperature: -30 … +60 °C
  • Inputs: internal humidity, temperature and CO2 sensor
  • Power: 9-30 V DC
  • Protection class: IP 30 electronics, IP 40 sensors
  • dimensions: 136 x 213 x 45 mm
COMET

Description

H6020 Temperature, humidity and CO2 controller with two relay outputs.

The controller contains a microprocessor-based control circuit, housed in a rugged plastic enclosure with connection terminals. The sensor is equipped with a stainless mesh filter. Computer processing allows long-term stability and error display. The H6020 has a built-in capacitive polymer sensor for long-term calibration stability, independent of water and condensation.

The measured values can also be converted into other formats such as dew-point temperature, absolute humidity, specific humidity, mixing ratio or others.

Indoor carbon dioxide levels are often an important indicator of air quality.

Especially in buildings where several people are present at the same time. For example in schools, conference rooms, cinema halls, theatres and hospitals. A carbon dioxide sensor can help improve indoor air quality.


Visual display of CO2 concentration in the air

  • green: CO2 concentration 0 … 1000 ppm
  • bright yellow: CO2 concentration 1001 … 1200 ppm
  • illuminated red: CO2 concentration 1201 ppm or more

 

Features H6020

Temperature sensor

  • measuring range: -30 … +80 °C
  • Accuracy: ±0.4 °C
  • resolution: 0.1 °C

Humidity sensor

  • measuring range: 0 … 100 % RH
  • Accuracy: ±2.5 % RH at 5 … 95 % and 23 °C
  • resolution: 0.1 % RH

Rosišče (dew point)

  • measuring range: -60 … +80 °Cdp
  • Accuracy: ±1.5 °Cdp at room temperature T<25 °C and RH>30%
  • resolution: 0.1 °C

CO2 sensor

  • measuring range: 0 … 2000 ppm
  • Accuracy: ±50 ppm + 2 % of reading at 25 °C and 1013 hPa
  • resolution: 1 ppm

RELATED EXITS

  • quantity: 2
  • maximum voltage: 50 V
  • maximum current: 2 A
  • Maximum power: 60 VA

 

GENERAL TECHNICAL DATA

  • ambient temperature: -30 … +60 °C
  • Inputs: internal humidity, temperature and CO2 sensor
  • Power: 9-30 V DC
  • Protection class: IP 30 electronics, IP 40 sensors
  • dimensions: 136 x 213 x 45 mm
  • Stem length: 75 mm
  • weight: 360 g
  • Warranty: 3 years
  • Set includes: the H6020, user manual, calibration certificate with traceability and FREE TSensor software to configure the inverter

 