T0213D relative humidity and temperature transmitter for duct mounting with 0-10 V COMET output
Po naročilu. Pošljite povpraševanje.
Delivery time: okvirno 2 tedna
Temperature
- measuring range: -30 … +125 °C
- Accuracy: ±0.4 °C
Invests
- measuring range: 0 … 100 % RH
- Accuracy: ±2.5 % RH from 5 to 95 % at 23 °C
General information
- ambient temperature: -30 … +80 °C
- Output: 0-10 V
- Power: 15-30 V DC; 24 V AC
- Protection class: IP 65 electronics; IP 40 sensors
- dimensions: 88,5 x 250 x 39,5 mm
Description
T0213D relative humidity and temperature transmitter for duct mounting for indoor and outdoor use with 0-10 V output.
The T0213D transducer contains a microprocessor-based control circuit in a rugged plastic housing with connection terminals. The measured values can also be converted into other interpretations of humidity: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy. The sensor contains a stainless mesh filter.
The built-in capacitive polymer humidity sensor ensures long-term stability of the humidity calibration, independent of the influence of water and condensation. Computer processing allows temperature compensation of the humidity sensor and error display. The converter is useful for measurements in a non-aggressive environment.
Features of T0213D
Temperature sensor
- measuring range: -30 … +125 °C
- Accuracy: ±0.4 °C
- resolution: 0.1 °C
Humidity sensor
- measuring range: 0 … 100 % RH
- Accuracy: ±2.5 % RH from 5 to 95 % at 23 °C
- resolution: 0.1 % RH
Rosišče (dew point)
- measuring range: -60 … +80 °Cdp
- Accuracy: ±1.5 °Cdp at room temperature T<25 °C and RH>30%
- resolution: 0.1 °Cdp
GENERAL TECHNICAL DATA T0213D
- ambient temperature: -30 … +80 °C
- Input: internal temperature and humidity sensor
- Output: 0-10 V
- Power: 15-30 V DC; 24 V AC
- Protection class: IP 65 electronics; IP 40 sensors
- dimensions: 88,5 x 250 x 39,5 mm
- Stem length: 150 mm
- weight: 150 g
- Warranty: 3 years
- Set includes: the T0213D, user manual, calibration certificate with traceability, FREE TSensor software to configure the transducer
Areas of use, applications
- Building automation and HVAC management,
- warehouses,
- greenhouses,
- production facilities,
- museums/archives/galleries,
- air-conditioned rooms,
- weather stations.
The converters are approved and homologated by RENAULT and PSA (PEUGEOT / CITROEN).
You can find much more useful information in the Documentation tab.
Articles
You are invited to read our article
”World Meteorology Day – Precision Measurements in Meteorology”
.
Povpraševanje
You may also like…
For your victories, with our solutions. Call us:
Contact us.
Call us:
+386 (0)2 62 96 720
Email us:
[email protected]