  • supply voltage: standard 230 V AC; on request: 115 V AC, 24 V AC, 24 V DC and 12 V DC
  • Functionality: on the principle of quiescent or operating current
  • temperature range: -20°C to 60°C
  • IP degree of protection: IP 20
  • housing: insulating material, 75 x 55 x 110mm
za merjenje nivoja tekočin, detekcija uhajanja

Description

The NR 5/Ex electrode relay EX JOLA is designed to transmit control commands. They shall be installed in a control cabinet or other suitable protective enclosure. The switches are suitable for use in clean environments.

Relay with electrodes for mounting or DIN rail mounting via 2 drill holes, with connection terminals on top of the housing and with 2 built-in LEDs for alarm status indication.

The unit is designed for installation or installation of the switch box in a suitable protective enclosure outside potentially explosive atmospheres and can therefore only be installed in these locations. It is only suitable for use in clean environments.

Electronic relay NR 5 / Ex I (M1) / II (1) GD [Ex ia Ma] I / [Ex ia Ga] IIC / [Ex ia Da] The IIIC is designed to transmit control commands from an intrinsically safe control circuit to a non-isolated safe active current circuit. It must be installed outside potentially explosive areas in accordance with the relevant standards and regulations.

Ex ia II. T6 G. approved conductive electrodes such as types EL….. Ex II 2 G or II 1 G Ex ia II. T6 G., can be used in a truly safe control current circuit. The various application possibilities and the special conditions for safe use are described in the relevant installation, operation and maintenance instructions (sent on request).

Electrode relay Ex NR 5 / Ex I (M1) / II (1) GD [Ex ia Ma] I / [Ex ia Ga] IIC / [Ex ia Da] IIIC, based on the quiescent current principle: in OK state, the output relay is energised.

Electrode relay NR 5 / Ex I (M1) / II (1) GD [Ex ia Ma] I / [Ex ia Ga] IIC / [Ex ia Da] IIIC version A, based on the operating current principle: in OK state, the output relay is not energised.

Feature NR 5/Ex

Technical data NR 5/Ex I (M1) / II (1) GD [Ex ia Ma] I / [Ex ia Ga] IIC / [Ex ia Da] IIIC NR 5/Ex I (M1) / II (1) GD [Ex ia Ma] I / [Ex ia Ga] IIC / [Ex ia Da] IIIC Version A
Supply voltage 230 V AC (other voltages on request; see datasheet)
Power of the entrance approx. 3 VA approx. 3 VA
electrode circuit 3 terminals (under safety extra-low voltage SELV) operating on 1 output relay 3 terminals (under safety extra-low voltage SELV) operating on 1 output relay
no-load voltage 3 Veff 10 Hz 3 Veff 10 Hz
short-circuit current max. 0.5 mAeff max. 0.5 mAeff
sensitivity of response approx. 30 kW or approximately 33 µS (conductivity) approx. 30 kW or approximately 33 µS (conductivity)
control circuit 1 single-pole potential-free switching contact with self-restraint 1 single-pole potential-free switching contact with self-restraint
functionality according to the principle of quiescent current by the principle of operating current
status indicators 1x green LED(on), 1x red LED(off) 1x green LED(on), 1x red LED(off)
switching voltage max. 250 V AC max. 250 V AC
switching current max. 4 A AC max. 4 A AC
switching power max. 100 VA max. 100 VA
housing insulation material, 75 x 55 x 110 mm insulation material, 75 x 55 x 110 mm
Link terminals on the housing terminals on the housing
protection class IP20 IP20
installation on 35 mm DIN rail or fixing via 2 drill holes on 35 mm DIN rail or fixing via 2 drill holes
orientation of the installation any any
temperature range -20 °C to +60 °C -20 °C to +60 °C
EC type-examination certificate INERIS 03ATEX0151 INERIS 03ATEX0151